• image

6181B BS 7211 SC

Application

  • POLYCAB 6181B BS 7211 SC stranded copper conductor thermosetting material insulated and halogen free material sheathed single core cable fulfils the requirement as per BS 7211. These cables are produced lower level of smoke and corrosive gases under exposure to fore compared PVC insulated cable and can be used for lighting and domestic appliances.

Voltage Rating

  • – 450/750 V

Operation Temperature

  • – Max. Operating: 90°C
  • – Short circuit temperature: 250°C

Construction

  • – Annealed solid or stranded copper conductor as per IEC 60228, class 1 or class 2
  • – Insulated with Cross linked compound Type GP 8 confirming to BS 7655-1.3 or EI 5 to BS EN 50363-5
  • – Sheathed with Halogen free material type LTS4 confirming to BS 7655-6.1

Core Identification

  • – Brown or Blue

Bending Radius

  • – Fixed installation – 8 x Overall Diameter
  • – Occasional – 6 x Overall Diameter

Standard and References

  • – IEC 60228
  • – BS 7655-1.3/BS EN 50363-5
  • – BS 7655-6.1
  • – BS 7211:1998