BS 7870-4-10
Application
- POLYCAB MV AL BS 7870-4-10 8.7/15 KV XLPE insulated with aluminium conductor single & multi core cable is designed for low smoke & low halogen evolution and this suitable to use for power networks, underground and in cable ducting.
Voltage Rating
- – Nominal Voltage: 6.35 /11 kV
Operation Temperature
- – Max. operating temperature: +90°C
- – Max. Short Circuit Temperature: 250°C
Construction
- – Conductor: Stranded Aluminium as per Class 2 of BE EN 60228
- – Conductor Screen: Extruded Semi-conductive compound
- – Insulation: XLPE Type DIX 3 as per BS 7870-1
- – Non-Metallic Insulation Screen: Extruded Semi-conductive compound
- – Metallic Insulation Screen: Copper tape screen
- – Outer sheath: MDPE Type 'DMP5' as per BS 7870-1
Standard Reference
- – BS EN/IEC 60228
- – BS 7870-1